Breaker-failure protection
ABB Network Partner AB
1MRK 580 171-XEN
Page
5 - 89
Version 1.0-00
2.5 Back-up trip
The back-up trip delay timer t2 can be set between 50 and 400 ms.
A trip pulse length of 150 ms is generated.
Fig. 7
Breaker-failure protection
3 Setting
3.1 Man-machine
interface (MMI)
The configuration of alternatives or settings to the functions is made on
the built-in MMI:
Settings
Functions
Group n
Breaker Failure
The breaker-failure protection can be controlled from the man-machine
interface (MMI) by an “Operation” parameter, to be set between alterna-
tives Off/On.
When “Operation” is set to Off, the function becomes inoperative.
The configuration of input and output signals to the function is made on
the built-in MMI:
Configuration
Function Inputs
Breaker Failure
(X80171-7)
1
V
TTRIP
STARTL1
BUTL1
RTL1
L1
RETRIPL1
1
V
TTRIP
STARTL2
BUTL2
RTL2
RETRIPL2
1
V
TTRIP
STARTL3
BUTL3
RTL3
RETRIPL3
IL1
StartL1
IL2
StartL2
StartL3
IL3
Start3ph
L2
L3
1
V
TTRIP
BACK-UP
TRIP
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......