ABB Network Partner AB
Disturbance report - Introduction
Version 1.0-00
1MRK 580 132-XEN
Page 7
-
56
4.1 Trig signals
The trig conditions affect the entire disturbance report. As soon as a trig
condition is fulfilled, a complete disturbance report is recorded. On the
other hand, if no trig condition is fulfilled, there is no disturbance report,
no calculation of distance to fault, no indications, and so on. This implies
the importance of choosing the right signals as trig conditions.
A trig can be of type:
• Manual trig
• Binary-signal trig
• Analogue-signal trig (over/under function)
4.1.1 Manual trig
Manual trig starts from the built-in MMI or from a front-connected PC (or
SMS). This is found on the MMI menu tree at:
DisturbReport
Manual Trig
4.1.2 Binary trig
A trig on a binary signal can be activated on either a logical 1 or a
logical 0. When a binary input is used as trig, the signal must stay for at
least 15 ms to be picked up.
Note that when a binary signal is programmed to trig on a logical 0, this
signal is not presented as an indication in the disturbance report.
4.1.3 Analogue trig
All analogue signals are available for trigger purposes, no matter if they
are recorded in the disturbance recorder or not. But the Disturbance
Recorder function must be installed in the terminal.
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......