ABB Network Partner AB
Direct current measuring unit
Version 1.0-00
1MRK 580 154-XEN
Page 7
-
6
User can this way select for each measuring quantity on each monitored
object of a power system the most suitable measuring range and this way
optimise a complete functionality together with the characteristics of the
used measuring transducer.
3 Continuous monitoring of the measured quantity
The user can continuously monitor the measured quantity in each channel
by means of six built-in operating limits, see Fig. 1. Two of them are
defined by the selection of operating range: I_Max as the upper and
I_Min as the lower operating limit. The other four operating limits oper-
ate in two different modes of operation:
• Overfunction, when the measured current exceeds the HiWarn or
HiAlarm pre-set values
• Underfunction, when the measured current decreases under the Low-
Warn or LowAlarm pre-set values
Fig. 1
Presentation of the operating range and operating limits
Each operating level has its corresponding functional output signal (FOS).
Its logical value changes according to Fig. 1.
You can set the hysteresis, which determines the difference between the
operating and reset value at each operating point, in wide range for each
measuring channel separately. The hysteresis is common for all operating
values within one channel.
4 Continuous supervision of the measured quantity
The actual value of the measured quantity is available locally and
remotely. The measurement is continuous for each channel separately.
But the reporting of the value to the higher levels (control processor in the
module, MMI and SCS) depends on the selected reporting mode.
I_Max
HiAlarm
HiWarn
LowWarn
LowAlarm
I_Min
RMAXAL=1
HIALARM=1
HIWARN=1
RMAXAL=0
HIALARM=0
HIWARN=0
LOWWARN=0
LOWALARM=0
RMINAL=0
RMINAL=1
LOWALARM=1
LOWWARN=1
Hysteresis
Y
t
(X80154-1)
Содержание REC 561
Страница 19: ...ABB Network Partner AB Introduction REC 561 Version 1 0 00 1MRK 580 146 XEN Page 2 14 ...
Страница 31: ...ABB Network Partner AB Requirements and basic technical data REC 561 Version 1 0 00 Page 2 26 ...
Страница 49: ...ABB Network Partner AB Page IV ...
Страница 67: ...ABB Network Partner AB Installation and commissioning Version 1 0 00 1MRK 580 166 XEN Page 3 18 ...
Страница 85: ...ABB Network Partner AB Local man machine communication Version 1 0 00 1MRK 580 156 XEN Page 3 36 ...
Страница 121: ...ABB Network Partner AB Menu tree Appendix Version 1 0 00 1MRK 580 158 XEN Page 3 72 ...
Страница 139: ...ABB Network Partner AB Terminal identification Version 1 0 00 1MRK 580 160 XEN Page 4 4 ...
Страница 143: ...ABB Network Partner AB Activation of setting group Version 1 0 00 1MRK 580 162 XEN Page 4 8 ...
Страница 175: ...ABB Network Partner AB Configurable logic Version 1 0 00 1MRK 580 161 XEN Page 4 40 ...
Страница 261: ...ABB Network Partner AB Auto reclosing Single and or three phase Version 1 0 00 1MRK 580 170 XEN Page 5 82 ...
Страница 281: ...ABB Network Partner AB Loss of power system voltage Version 1 0 00 1MRK 580 153 XEN Page 5 102 ...
Страница 385: ...ABB Network Partner AB Apparatus control Version 1 0 00 1MRK 580 150 XEN Page 6 100 ...
Страница 495: ...ABB Network Partner AB Interlocking Version 1 0 00 1MRK 580 151 XEN Page 6 210 ...
Страница 515: ...ABB Network Partner AB Event function Version 1 0 00 1MRK 580 140 XEN Page 6 230 ...
Страница 519: ...ABB Network Partner AB Page IV ...
Страница 561: ...ABB Network Partner AB Time synchronisation Version 1 0 00 1MRK 580 135 XEN Page 7 42 ...
Страница 569: ...ABB Network Partner AB Internal events Version 1 0 00 1MRK 580 134 XEN Page 7 50 ...
Страница 599: ...ABB Network Partner AB Index Version 1 0 01 1MRK 580 175 XEN Page 8 6 ...
Страница 634: ......
Страница 635: ......
Страница 636: ......
Страница 637: ......
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......