8-4
8. TROUBLESHOOTING
8.2 Flow (Only for /MV)
●
Start with this flow in case of /MV.
Are the power polarities
Correct?
Are the load resistance
and supply voltage within
the tolerance limits?
Check the polarities.
No
Yes
No
Are the sensor
connected correctly?
Yes
Adjust to within the tolerance limits.
Yes
Yes
No
Are the parameters
confiured correctly at
operational conditions?
Configure the parameters correctly.
No
Go to “8.1 Flow”
F080201.EPS
Yes
Was a faulty area
found with self-diagnostic?
No
Refer to the error code list and check
for recovery measures.
• If a built-in indicator is attached,
check the display of the error
code.
• Connect a hand-held terminal and
check self-diagnostic.
Check the sensor.