4. WIRING
Table 4.3
Finishing the Signal Cable End(DYC) (For Vortex Flow Converter DYA)
1
2
3
4
5
6
7
8
9
Do not short - circuit the conductive layer and the
terminals.
Insert black FEP insulation tubing over inner shield
until it stops inside the braided shield.
Cut the tubing off leaving only 5mm of the inner
shield exposed.
Remove 5mm of insulation from the tips of the two
wires.
Insert the heat-shrinkable tubes as shown.
Put heat-shrinkable tubes on yellow
(*1)
, red, white,
black.
Crimp the chip to each wire end and then solder.
Affix the label as shown.
Confirm that the insulation resistance between each
wire including the inner shield is 10Mohm or greater
at 500VDC. Maintain both ends of the wires
disconnected(open - circuited) during the insulation
resistance test.
T040402.EPS
Description
Figure
Unit : mm
Black tube
Blue tube
Heat-shrinkable tubes
Heat-shrinkable tubes
95
10
10
White
Red
Heat-shrinkable tubes
Solder
Tips
10
Remove the outer polyethylene jacket, outer
braided shield and inner jacket, inner braided shield
as per the dimensions as shown.
Cut of the black conductive layers(convering the
two wires) completely, as per the dimensions below.
Twist each of the conductor and drain wires so that
there are no free strands.
Remove the red and white insulation as per the
dimensions as shown.
Shrink the heat-shrinkable tubes by heating with a
drier etc.
50
60
3MAX
5
5
5
5
15
25
40
5
Yellow
(*1)
(*1): Only for /MV
Black
Conductive Layer
Black Conductive Layer
(A)
RED
(B)
WHITE
BLACK (C)
(G)
BLUE
Unit : mm
F040406.EPS
70
95
60
80
120
10
10
5
MAX
3
YELOW(T) 50
Figure 4.8
CAUTION
Do not touch the '' conductive layer" (black area covering the signal cables A and B) to the converter case, terminal,
and other leadwires. If it is touched, operation of the converter may be incorrect. When the cable is terminated,
remove the conductive layer properly.