Traverse Installation and Commissioning Guide, Section 9: Alarm, Timing, and Management Cabling Procedures
PDAP-15A Fuse Alarm Connections
Page 9-22
Turin Networks
Release TR3.2.1
PDAP-15A
Fuse Alarm
Connections
Follow these steps to complete fuse alarm connections at PDAP-15A.
Important:
Always wear a properly Electrostatic Discharge (ESD) wrist
strap when making alarm wire connections to the PDAP-15A.
Table 9-13 Connect PDAP-15A Fuse Alarms
Step
Procedure
1
Two alarm wires are required for visual and audible fuse alarms,
normally-open (NO) and common (C) or normally-closed (NC) and
common (C). Strip back the insulation by 3/4 inch (7 mm) exposing
enough wire to make a minimum of five turns.
2
Fuse alarm wires are connected to wire-wrap posts on the back of the
PDAP-15A. Terminate the visual fuse alarm wires using a wire-wrap tool.
Figure 9-17 PDAP-15A Fuse Alarm Input Wire-Wrap Posts
3
Repeat Steps 1 and 2 for the audible fuse alarm wires.
4
Route wires to the CO fuse alarm panel following local procedures.
5
Connect visual and audible fuse alarm wires to the CO fuse alarm panel
following local procedures.
Note:
Two wires are required for each fuse alarm (normally-open and
common or normally-closed and common).
6
The Connect PDAP-15A Fuse Alarms procedure is complete. Continue to
the Connect PDAP-15A Visual Alarm Inputs procedure.