Chapter 1 Traverse System Rack Installation Overview
Grounding the Shelf and Fan Tray Holder
Release TR3.2.1
Turin Networks
Page 7-3
Traverse Shelf
Back Covers
The Traverse shelf has removable back covers to provide access to the fiber optic
backplane, main backplane, and front inlet fan tray holder connector. The covers are
easily removed for cabling, but must be replaced during normal operation to ensure
proper air flow and electromagnetic interference (EMI) protection. Refer to
Section 6—
Precautions and Common Procedures
Replacing Back Covers,” page 6-9.
Grounding the
Shelf and Fan
Tray Holder
The Traverse shelf and fan tray holder are grounded to the rack using thread-forming
screws (minimum of three per side) and conductive plated rack adapters for Traverse
1600 23-inch (584 mm) or Traverse 2000 19-inch (483 mm) rack installation. No
additional grounding procedures are required when installed in a properly grounded
telco rack.
Figure 7-1 Grounding Terminals on Backplane
Important:
For NEBS compliance, remove paint and any other
non-conductive coatings on the surfaces between the mounting hardware
and the rack framework. Clean all surfaces and apply an antioxidant
before joining.
WARNING!
The grounding terminals on the backplane are for power
terminal cables only and SHOULD NOT be used for chassis
grounding.
For power terminal cables only!
WARNING! DO NOT use f
cabinet or rack groundin