Chapter 5 Ethernet (Electrical) Cabling Procedures
Unprotected 10/100BaseTX Cabling at the Electrical Connector Module
Release TR3.2.1
Turin Networks
Page 8-47
8
Tie-wrap cables to the cable management bar following local procedures.
Figure 8-23 Traverse Shelf with Cable Management Bar(s)
9
Route the 10/100BaseTX cables to the intermediate patch panel located in
the same or adjacent rack per local procedures.
10
Cut 10/100BaseTX cables to the correct length using cable cutters.
Important:
The Turin Telco 50 cable assembly is shielded. Connect a
ground wire to the shielding. Connect the ground wire to the equipment
rack following local procedures.
11
Use a wire wrap tool to terminate 10/100BaseTX cables at the patch panel;
or terminate cable/pairs onto RJ-45 connectors for termination at the patch
panel.
1
12
Use category 5 twisted-pair patch cable between the patch panel and
10/100BaseT network equipment.
13
The Protected GbE TX and 10/100BaseTX Cabling at the ECM procedure
is complete.
Do you have other network interface connections?
•
Yes.
Repeat ECM and cabling connections for all network interfaces.
•
No.
Alarm, Timing, and Management Cabling
, Chapter 1—“Alarm Interface Cabling”.
1
Turin provides an optional snap-in faceplate patch panel for termination of fiber optic cables (SC duplex
module) and Category 5 cables (RJ-45). This patch panel is used for the Ethernet Combo module. It
provides flexibility and better identification of pairs terminated at the intermediate patch panel. Turin
part number 950-0070-00 (2-port SC Duplex Adapter, 16-port 10/100 Ethernet Category 5 Module).
Table 8-17 Unprotected 10/100BaseTX Cabling, Electrical Connector Module
Step
Procedure
Cable
management
bars
Cables to the
right or left