RT-SVP07B-EN
85
SETPOINT Menu
The setpoint menu is used to designate default zone temperature setpoints, supply air and space pressure setpoints, and
low ambient compressor lockout setpoints.
These setpoints will be active (in use) for the “Setpoint Source Selection” designated as “DEFAULT” for these inputs.
When a setpoint screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general
operating status display. If this happens, press the
Setpoint
key again to return to the setpoint menu.
Note:
Many of the screens displayed in this section are applicable only for the options that are installed in the unit and
may not be visible on your unit.
Modifying Selections:
Starting with the first setpoint screen program the necessary information by using the
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has been
changed to the desired value, the user has the following options to either
Cancel
or
Accept
the pending change:
•
To
Cancel
, press the
Cancel
key to remove the change, the display will revert to the original value.
•
To
Accept
, press the
Enter
key to confirm the new choice.
Press the
Setpoint
key to begin viewing or modifying the unit setpoints.
TOP LEVEL SETPOINTS SCREEN
Default Supply Air Temp Setpoints
Cooling: 55°F Heating: 100°F
Used With: VV/CVDA or VVZT Units
Factory Presets: Factory Presets:
Cooling: 55ºF (VVZT: 50°F)
Heating: 100ºF (VVZT: 105°F)
Possible Values:
Cool: 40 to 90ºF
Heat: 40 to 180ºF
Note:
These values must be reset on field replacement of the RTM
Module if the unit is configured for SZVAV (VVZT).
“Heating” setpoint only shown if units are configured with hydronic
or modulating gas heat, or if IpakII w/electric heat.
• Press Next/Previous keys to navigate.
Supply Air Temperature Deadband
Cooling: 8.0°F Heating: 4.0°F
Used With: VV/CVDA Units
Factory Presets:
Cooling: 8ºF
Heating: 4ºF
Possible Values:
Cool: 4 to 20ºF
Heat: 2 to 10ºF
“Heating” setpoint only shown if units are configured with hydronic
or modulating gas heat, or if IpakII w/electric heat.
• Press Next/Previous keys to navigate.
Default Daytime Warmup Setpoints
Initiate: 67°F Terminate: 71°F
Used With: VV/CVDA Units w/DWU
Enabled
Factory Presets:
Initiate: 67ºF
Terminate: 71ºF
Possible Values:
DWU Initiate: 50 to 87ºF
DWU Terminate: 53 to 90ºF
• Press Next/Previous keys to navigate.