108
RT-SVP07B-EN
SERVICE MODE Menu (Local Human Interface only)
Condenser Sump Drain Relay: OFF
Condenser Sump Drain Valve: CLOSED
Used With: Units w/Water-Cooled
Condensers
Possible Values:
Relay: OFF, ON
Valve: CLOSED, OPEN (Display Only)
Note: The valve state is based on the
power loss configuration of the drain
valve. [See “
Table 7: Sump Drain Valve
States
on Left”]
Table 7: Sump Drain Valve States
Drain Relay Cmd
Power Loss Config
Valve State
OFF
HOLD
CLOSED
OFF
DRAIN
OPEN
ON
HOLD
OPEN
ON
DRAIN
CLOSED
• Press Next/Previous keys to navigate.
Condenser Sump Fill Relay: ON
Condenser Sump Fill Valve: OPEN
Used With: Units w/Water-Cooled
Condensers
Possible Values:
Relay: OFF, ON
Valve: CLOSED, OPEN (Display Only)
• Press Next/Previous keys to navigate.
Sump Heater Relay: OFF
Used With: Units w/Water-Cooled
Condensers and Sump Heat Installed
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Condenser Sump Pump Relay: OFF
Used With: Units w/Water-Cooled
Condensers
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Condenser Fan Outputs
K1: OFF K2: OFF
Used With: Units w/DX Cooling < 40
Tons, and Airside Condensers Installed
Possible Values: ON, OFF, AUTO
Note: If either K1 or K2 is set to AUTO, the other will
automatically be changed to AUTO.
• Press Next/Previous keys to navigate.
Condenser Fan Outputs (MCM 1)
K1: OFF K2: OFF K5: OFF K6: OFF
Used With: Units w/DX Cooling > 40
Tons, and Airside Condensers Installed
Possible Values: ON, OFF, AUTO
Note:
1. If either K1 or K2 is set to AUTO, the other will automatically be
changed to AUTO.
2. If either K5 or K6 is set to AUTO, the other will automatically be
changed to AUTO.
• Press Next/Previous keys to navigate.