SERVICE MODE Menu (Local Human Interface only)
Modulating Gas Heat
Actuator 0%
Used With: Modulating Gas Heat Units,
(If Air Handler Unit, Chill Water Is Not
Installed)
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
Heat Stages: 0
K11: OFF K12: OFF K1: OFF
Used With: Units w/Staged Gas or
Electric Heat Option
Possible Values:
Stages: 0, 1, 2, 3, 4, 5
[Config. Dependent-see “
Table 10:
Electric Heat Relay States
”]
• Press Next/Previous keys to navigate.
OA Damper: 0% Exhaust Damper: 0%
Exhaust Fan: OFF
Used With: All Units
Possible Values:
OA Damper:
0 to 100% (Economizer Option)
0 to 25% (Motorized Damper Option)
Exhaust Damper: 0 to 100%
Exhaust fan: OFF, ON
“OA Damper” shown if Economizer or 25% Damper installed.
“Exhaust Damper” shown if Power Exhaust w/Statitrac installed.
“Exhaust Fan” shown if Power Exhaust w/o Return Fan installed.
• Press Next/Previous keys to navigate.
Ventilation Override Module Output Relay
OFF
Used With: Units w/VOM Option
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
VCM Preheater State OFF
Used With: Units w/Fresh Air
Measurement (VCM) Option
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
GBAS 0-5VDC Module Relay Outputs
#1 OFF #2 OFF #3 OFF #4 OFF #5 OFF
Used With: Units w/GBAS(5VDC)
Option
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
Table 10: Electric Heat Relay States
All Units
Gas Heat
IntelliPak I
Electric Heat
IntelliPak II
90 KW
140 KW
265/300 KW
Stage K11 K12 K1 K11 K12 K1
K11
K12
K1
K11
K12
K1
K11
K12
K1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Stage 1
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
Stage 2
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
Stage 3
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
Stage 4
ON
ON
ON
OFF
ON
ON
Stage 5
ON
ON
ON