![Trane S*HF*20-75 Troubleshooting Manual Download Page 57](http://html1.mh-extra.com/html/trane/s-hf-20-75/s-hf-20-75_troubleshooting-manual_1149487057.webp)
RT-SVP07B-EN
57
SETUP Menu
Evap Temperature Limit. Shut Off Circuit
if (Leaving - Entering) Exceeds: 35ºF
Used With: All Units
Factory Preset: 35ºF
Possible Values: 25 to 40ºF
Note:
On units with Dehumidification installed a non-adjustable
Evap Temperature Limit of 40ºF is used for the Reheat Circuit only.
• Press Next/Previous keys to navigate.
Coil Frost Cutout Temperature. Shut off
Compressors If Evap Temp Is Below: 30ºF
Used With: Units w/DX Cooling
Factory Preset: 30ºF
Possible Values: 25 to 35ºF
• Press Next/Previous keys to navigate.
Isolation Damper Interlock: ENABLED
SA Proving Must Open Before Fan Start
Used With: All Units
Factory Preset: DISABLED
Possible Values: DISABLED, ENABLED
If ENABLED, “SA Proving Must Open Before Fan Start” is shown. If
DISABLED, the bottom line is blank.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
VAV CONTROL FUNCTIONS SUBMENU SCREENS
VAV Control Functions Submenu
Press ENTER to Review or Adjust
Used With: All Units
Press the Next key to skip this Submenu.
Supply Air Temp Reset type:
Cooling: NONE Heating: NONE
Used With: VV/CVDA Units w/Cooling
and Heat Installed
Factory Preset: NONE
Possible Values: NONE, ZONE, OA
“Heating” only shown if unit has heat installed.
• Press Next/Previous keys to navigate.