RT-SVP07B-EN
87
SETPOINT Menu
Stop Dehumid if Space RH Below STP Minus
Occ Dehumid Hysteresis Offset: 5%
Used With: Units w/Dehumidification
Option
Factory Preset: 5 %
Possible Values: 3 to 10 %
• Press Next/Previous keys to navigate.
Dehumidify if Space Humidity Above
Unocc Dehumidification Setpoint: 60%
Used With: Units w/Dehumidification
Option and Unocc Dehumid. Enabled
Factory Preset: 60 %
Possible Values: 40 to 65 %
• Press Next/Previous keys to navigate.
Stop Dehumid if Space RH Below STP Minus
Unocc Dehumid Hysteresis Offset: 5%
Used With: Units w/Dehumidification
Option and Unocc Dehumid. Enabled
Factory Preset: 5 %
Possible Values: 3 to 10 %
• Press Next/Previous keys to navigate.
Default Supply Air Reheat Stpt: 70°F
Supply Air Reheat Deadband: 4°F
Used With: Units w/Dehumidification
Option
Factory Preset:
Reheat Setpoint: 70ºF
Reheat Deadband: 4ºF
Possible Values:
Reheat Setpoint: 60 to 80ºF
Reheat Deadband: 2 to 10ºF
• Press Next/Previous keys to navigate.
In Active Dehumidification Mode, Limit
Maximum Reheat Valve Position To: 85%
Used With: Units w/Dehumidification
Option
Factory Preset: 85 %
Possible Values: 50 to 85 %
• Press Next/Previous keys to navigate.
Dehumid Ovrd High Zone Temp Stpt: 75°F
Dehumid Ovrd Low Zone Temp Stpt: 68°F
Used With: VV/CVDA Units w/
Dehumidification Option
Factory Preset:
Ovrd High Temp: 75ºF
Ovrd Low Temp: 68ºF
Possible Values:
Ovrd High Temp: 70 to 85ºF
Ovrd Low Temp: 60 to 75ºF
• Press Next/Previous keys to navigate.
Cond Coil Purge Interval Setpt: 90 Min
Used With: Units w/Dehumidification
Option
Factory Preset: 90 Minutes
Possible Values: 60 to 120 Minutes
• Press Next/Previous keys to navigate.