RT-SVP07B-EN
47
STATUS Menu
Active Supply Air Press Input From
RTM SA PRESSURE INPUT is 2.1 IWC
Used With: VVDA or Units w/Supply Air
Pressure Sensor Present
Possible Values:
RTM SA PRESSURE INPUT
BAS/NETWORK
Range: 0 to 7.9 IWC
• Press Next/Previous keys to navigate.
Active Space Pressure Input From
ECEM SPACE PRESSURE INPUT is 0.08 IWC
Used With: Units w/Statitrac Option
Possible Values:
ECEM SPACE PRESSURE INPUT
BAS/NETWORK
Range: -0.67 to 0.67 IWC
• Press Next/Previous keys to navigate.
Temp Sensor Input Being Monitored:
RTM ZONE TEMP INPUT is 82.0°F
Used With: All Units
Possible Values:
RTM ZONE TEMP INPUT
NSB PANEL TEMP SENSOR INPUT
RTM AUX TEMP INPUT
HEAT MODULE AUX TEMP INPUT
ECEM RETURN AIR TEMP INPUT
BAS/NETWORK SENSOR
Range: -40 to 200ºF
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
TEMPERATURE INPUT STATUS SUBMENU SCREENS
Temperature Input Status Submenu
Press ENTER to View Data in This Submenu
Used With: All Units
• Press the Next key to skip this Submenu.
Temp Measured By Sensor Connected To
RTM SUPPLY AIR TEMP INPUT 50.0°F
Used With: All Units
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To
RTM ZONE TEMP INPUT 82.0°F
Used With: All Units
• Press Next/Previous keys to navigate.