RT-SVP07B-EN
67
SETUP Menu
•
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
•
Occupied/Unoccupied output - De-energized
•
VO Relay - Energized (with VOM module installed)
•
VCM Preheater State - Off (with VCM installed)
FIRE
•
Supply Fan – Off
•
Inlet Vanes - Closed (if equipped)
•
Return Fan / Exhaust Damper - Off / Closed (if equipped)
•
Return Fan VFD – Min
•
OA Dampers – Closed
•
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
•
Occupied / Unoccupied output - De-energized
•
VO Relay - Energized (with VOM module installed)
•
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode Definitions (with VOM installed)
Each of the five VOM modes have factory presets, that when initiated by a VOM contact closure, will accomplish five
predefined operations (listed below). Any of the five sequences may be user-redefined by changing the factory presets
at the unit mounted Human Interface or through Tracer.
Ventilation Override Mode A - (Unit Off)
•
Supply Fan – Off
•
Inlet Vanes / VFD - Closed / 0%
•
Return Fan VFD – Min
•
Return Fan / Exhaust Damper – Off / Closed (if equipped)
•
OA Dampers – Closed
•
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
•
Occupied / Unoccupied output – Deenergized
•
VO Relay – Energized
•
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode B - (Pressurize)
•
Supply Fan – On
•
Inlet Vanes / VFD - Open / 100%
•
Return Fan VFD – Min
•
Return Fan / Exhaust Damper - Off / Closed (if equipped)
•
OA Dampers – Open
•
Heat - All heat stages Off (staged gas & elec.); Hydronic heat & Mod Gas Heat output at 0%.
•
Occupied / Unoccupied output – Energized
•
VO Relay – Energized
•
VCM Preheater State - Off (with VCM installed)