58
RT-SVP07B-EN
SETUP Menu
Supply Air Temp Zone Reset For Cooling:
Start Temp: 72ºF End Temp: 69ºF
Used With: Units w/SA Cooling Reset
Type Set to “ZONE”
Factory Presets:
Start Temp: 72ºF
End Temp: 69ºF
Possible Values:
Start Temp: 51 to 90ºF
End Temp: 50 to 89ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Cooling:
Start Temp: 90ºF End Temp: 70ºF
Used With: Units w/SA Cooling Reset
Type Set to “OA”
Factory Presets:
Start Temp: 90ºF
End Temp: 70ºF
Possible Values:
Start Temp: 1 to 95ºF
End Temp: 0 to 94ºF
• Press Next/Previous keys to navigate.
Supply Air Temp Zone Reset For Cooling:
Maximum Amount of Reset Applied: 5ºF
Used With: Units w/SA Cooling Reset
Type Set to “ZONE”
Factory Presets: 5ºF
Possible Values: 0 to 20ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Cooling:
Maximum Amount of Reset Applied: 5ºF
Used With: Units w/SA Cooling Reset
Type Set to “OA”
Factory Presets: 5ºF
Possible Values: 0 to 20ºF
• Press Next/Previous keys to navigate.
Supply Air Temp Zone Reset For Heating:
Start Temp: 65ºF End Temp: 68ºF
Used With: Units w/SA Heating Reset
Type Set to “ZONE”
Factory Presets:
Start Temp: 65ºF
End Temp: 68ºF
Possible Values:
Start Temp: 50 to 89ºF
End Temp: 51 to 90ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Heating:
Start Temp: 10ºF End Temp: 60ºF
Used With: Units w/SA Heating Reset
Type Set to “OA”
Factory Presets:
Start Temp: 10ºF
End Temp: 60ºF
Possible Values:
Start Temp: 0 to 94ºF
End Temp: 1 to 95ºF
• Press Next/Previous keys to navigate.