SETUP Menu
Actuator Setup Supply Fan IGV/VFD Cmd
Max Voltage 10.0 VDC
Used With: VVDC Units
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Supply Fan IGV/VFD Cmd
Direct/Reverse Act DIRECT ACTING
Used With: VVDC Units
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD
Max Stroke Time 30 Sec
Used With: Units w/Return Fan Option
Factory Presets: 30 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD
Min Voltage 0.0 VDC
Used With: Units w/Return Fan Option
Factory Presets: 0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD
Max Voltage 10.0 VDC
Used With: Units w/Return Fan Option
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD
Direct/Reverse Act DIRECT ACTING
Used With: Units w/Return Fan Option
Factory Presets: Direct Acting
Possible Values: Direct, Reverse
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD
Max Stroke Time 60 Sec
Used With: Units w/Power Exhaust
Factory Presets: 60 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD
Min Voltage 2.0 VDC
Used With: Units w/Power Exhaust
Factory Presets: 2.0 VDC
Possible Values: 0 to 10.0 VDC
Note:
If the unit is configured for a Exhaust Fan VFD, initial setting
should be 0.0 VDC. If the unit is configured w/o VFD set this value
to 2.0 VDC.
• Press Next/Previous keys to navigate.