110
RT-SVP07B-EN
SERVICE MODE Menu (Local Human Interface only)
End Of Submenu (NEXT) For Service Mode
Used With: All Units w/DX Cooling
• Press Next/Previous keys to navigate.
Relay State = HEAT ON
Hydro Heat/Chilled Water Output 0%
Used With: Air Handlers w/Chilled
Water Cooling and Hydronic Heat
Possible Values:
Relay State:
HEAT ON, COOL ON, OVERRIDE
Output: 0 to 100%
Note: The relays on the HEAT module,
and associated wiring, are used to route
the 0 to 10VDC modulating output to the
Chill Water and Hydronic Heat actuators.
[See “
Table 8: Hydronic Heat/Chilled
Water Relay
on Left”]
Notes:
1. K1 turns ON when the output is commanded > 0%.
2.
Override occurs with Freezestat or service test request.
• Press Next/Previous keys to navigate.
Relay State = HEAT ON
Mod Gas Heat/Chilled Water Output 0%
Used With: Air Handlers w/Chilled
Water Cooling and Modulating Gas Heat
Possible Values:
Relay State: HEAT ON, COOL ON
Output: 0 to 100%
Note: The relays on the HEAT module,
and associated wiring, are used to route
the 0 to 10VDC modulating output to the
Chill Water and Mod Gas Heat actuators.
[see “
Table 9: Modulating Gas Heat /
Chilled Water Relay
on Left”]
Note: K1 turns ON when the output is commanded > 0%.
• Press Next/Previous keys to navigate.
Chilled Water
Actuator 0%
Used With: Air Handlers w/Chilled
Water Cooling (If Heating Unit, Hydronic
or Modulating Gas Is Not Installed)
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
Hydronic Heat
Actuator 0%
Used With: Hydronic Heat Units, (If Air
Handler Unit, Chill Water Is Not Installed)
Possible Values: 0 to 100%
• Press Next/Previous keys to navigate.
Table 8: Hydronic Heat/Chilled Water Relay
State/Relays
K11
K12
K1
OFF
OFF
OFF
OFF
Cool On
ON
ON
OFF
Heat On
OFF
OFF
Note 1
Override
ON
OFF
Note 2
Table 9: Modulating Gas Heat / Chilled Water Relay
State/Relays
K11
K12
K1
OFF
OFF
OFF
OFF
Cool On
OFF
OFF
OFF
Heat On
ON
OFF
Note 1
Override
OFF
OFF
OFF