RT-SVP07B-EN
91
SETPOINT Menu
Default Design Min OA Damper Pos: 15%
Default DCV Min OA Damper Pos Stp: 10%
Used With: Units w/OA Damper, And OA
Damper Min Pos w/DCV Option, and OA
CFM Compensation Disabled.
Factory Presets:
Design Min OA Damper: 15 %
DCV Min OA Damper: 10 %
Possible Values: 0 to 100 %
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 15%
With IGV/VFD Command At Minimum (0%)
Used With: VVDA or VVZT Units w/OA
Damper, And OA CFM Compensation
Enabled
Factory Presets:
VVDA: 15 %
VVZT: 25 %
Possible Values: 0 to 100 %
Note:
OA Damper Min Pos…At Minimum (0%) must be > OA
Damper Min Pos…At Maximum (100%) if VVDA, or at Medium
(50%) if VVZT.
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 20%
With IGV/VFD Command At Medium (50%)
Used With: VVZT Units w/OA Damper,
And OA CFM Compensation Enabled
Factory Presets: 20%
Possible Values: 0 to 100 %
Note:
OA Damper Min Pos…At Minimum (50%) must be > OA
Damper Min Pos…At Maximum (100%) and must be < OA Damper
Min Pos...At Minimum (0%).
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 10%
With IGV/VFD Command At Maximum (100%)
Used With: VVDA or VVZT Units w/OA
Damper, And OA CFM Compensation
Enabled
Factory Presets:
VVDA: 10 %
VVZT: 5 %
Possible Values: 0 to 100 %
Note:
OA Damper Min Pos…At Minimum (100%) must be < OA
Damper Min Pos…At Maximum (100%) if VVDA, or At Medium
(50%) if VVZT.
• Press Next/Previous keys to navigate.
OR
Default OA Damper Min Position: 15%
Used With: Units w/OA Damper Option,
DCV Disabled, OACFM Compensation
Disabled
Factory Presets: 15 %
Possible Values: 0 to 100 %
Note:
If unit has TRAQ, this setpoint is only used in case of flow
station failure.
• Press Next/Previous keys to navigate.
End Of Submenu (NEXT) To Enter SETPOINT
Used With: All units
• Press Next/Previous keys to navigate.