General Status Display
Factory Presets
The UCM controlled unit has many operating functions which are preset at the factory, but may be modified to meet the
unique requirements of each job. The following list in
Table 2
, identifies each of the unit’s adjustable functions and the
value assigned to it. If these factory presets match the application’s requirements, simply press the
Auto
key at the Human
Interface module to begin unit operation (after completing the Pre-Start and Start-Up procedures in the Installation,
Operation, and Maintenance manual). If the application requires different settings, turn to the listed page beside the
function, press the designated function menu key, then press and hold the
Next
or
Previous
key until its screen appears
on the LCD. Once the proper screen appears, simply follow the programming instructions given below the applicable
screen in this manual.
Note:
Listed items availability is dependent on unit configuration.)
Table 2.
Factory Presets List (Note: Listed Items availability is dependent on unit configuration.
Adjustable Function
Factory Preset
Changed To
To adjust
press...
General Function
Unit Address (Comm3/Comm4only)
1
___________
Setup
System Mode
Auto
___________
Setup
Supply Fan Mode
Auto
___________
Setup
Unit Start Delay
0
___________
Setup
Single Zone VAV Econ Control
Enabled
___________
Setup
Single Zone VAV Heat Control
Disabled
___________
Setup
Daytime Warm-up
Disabled
___________
Setup
Morning Warm-up
Enabled
___________
Setup
Morning Warm-up type
Cycling
___________
Setup
Supply Air Tempering
Disabled
___________
Setup
Unoccupied Mechanical Cooling
Enable
___________
Setup
Unoccupied Heating
Enable
___________
Setup
Unoccupied Mechanical Cooling
Enable
___________
Setup
Unoccupied Heating
Enable
___________
Setup
Occupied Dehumidification
Enable
___________
Setup
Unoccupied Dehumidification
Enable
___________
Setup
Occupied Humidification
Disable
___________
Setup
Unoccupied Humidification
Disable
___________
Setup
Rapid Restart Economizer Control
Disable
___________
Setup
VCM Preheat Output
Disable
___________
Setup
Demand Limit Definition - Cooling
None
___________
Setup
Demand Limit Definition - Heating
None
___________
Setup
Compressor Lead/Lag
Enable
___________
Setup
Evap Temperature Limit
35 F
___________
Setup
Coil Frost Cutout Temp
30 F
___________
Setup
Isolation Damper Interlock
Disable
___________
Setup
Information Format
Display Text
English
___________
Setup
Display Units
English
___________
Setup
VAV Control
SA Temp Reset Cool
None
___________
Setup