RT-SVP07B-EN
61
SETUP Menu
Sump Water Heater Setpoint: 38°F
Low Sump Temp Activates Heater Output
Used With: Units w/Water-Cooled
Condensers and Sump Heat Installed
Factory Preset: 38ºF
Possible Values: 38 to 43ºF
• Press Next/Previous keys to navigate.
Cond Temp Control Band
Lower Limit: 80°F Upper Limit: 120°F
Used With: Units w/DX Cooling
Factory Presets:
Upper Limit: 120ºF
Lower Limit: 80ºF
Possible Values:
Upper Limit: 110 to 130ºF
Lower Limit: 70 to 90ºF
• Press Next/Previous keys to navigate.
Cond Temp Control Band
Temporary Low Limit Suppression: 10°F
Used With: Units w/DX Cooling
Factory Presets: 10ºF
Possible Values: 0 to 20ºF
• Press Next/Previous keys to navigate.
Cond Temp
Efficiency Check Point: 105°F
Used With: Units w/DX Cooling
Factory Presets: 105ºF
Possible Values: 95 to 115ºF
• Press Next/Previous keys to navigate.
Cond Temp
Low Ambient Control Point: 90°F
Used With: Units w/DX Cooling w/Low
Ambient Option
Factory Presets: 90ºF
Possible Values: 80 to 100ºF
Low Ambient Dampers control condensing temperature to this
value.
• Press Next/Previous keys to navigate.
Alternate Unit Refrigerant Type: ENABLED
Used With: Units w/DX Cooling
Factory Presets: DISABLED
Possible Values: ENABLED/DISABLED
Units w/R22 should have this set to ENABLED
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.