72
RT-SVP07B-EN
SETUP Menu
Assign Diagnostic to Alarm Output 1?
Any Active Diagnostic (Yes)
Used With: All Units w/GBAS(5VDC)
Installed
Possible Values: Yes, No
Note:
If “Yes” is selected at this screen, any active diagnostic will
activate this output. A selection of “No” will allow the user to choose,
from the following menus, which diagnostics activate the Alarm
Output.
If No was entered, proceed to the following 2 screens.
Assignment Submenu – RTM Alarms
Press ENTER To Review Or Adjust
Used With: Units w/GBAS(5VDC) Installed
and Any Active Diagnostic Set to “No”
Note:
Please review the “Diagnostics
Troubleshooting Chart” in the
“DIAGNOSTICS Menu” section to see the
list of diagnostics associated with each
module. (Refer to the “Diagnostics
Displayed” column for the specified
module.)
Pressing the Next key will allow the user to skip this submenu.
Pressing the Enter key will allow the user to select any of the
diagnostics associated with the RTM module to activate the
associated Alarm Output.
Note:
The user will be presented with similar Assignment Submenus
for the following alarm sources: “SCM/MCM Alarms”, “HEAT Alarms”,
“ECEM Alarms”, “VOM Alarms”, “VCM Alarms”, “GBAS Alarms”, “MDM
Alarms”, “MPM Alarms” and “BAS/Network Alarms”.
If Enter was pressed, proceed to the following screen.
Assign Diagnostic to Alarm Output 1?
RTM Zone Temp Sensor Failure (Yes)
Used With: Units w/GBAS(5VDC)
Selecting “Yes” for each of the diagnostics displayed will activate the
associated Alarm Output when that diagnostic is activated.
Note:
The list of diagnostics displayed here will be dependent upon
the module assignments selected. See the “Diagnostics Table” in the
diagnostics menu section for the complete list displayed for each
module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter GBAS
• Press Next/Previous keys to navigate.
GBAS 0-10VDC MODULE I/O ASSIGNMENTS SCREENS
GBAS (10VDC) Module I/O Assignments
Press ENTER to Review or Adjust
Used With: Units w/GBAS(10VDC)
Installed
• Press the Next key to skip this Submenu.