DIAGNOSTICS Menu
Compressor Trip
(Ckt-1 or Ckt-2)
Used With: See
compressor protection
devices on MCM control
wiring schematic.
Module: MCM
Problem: The compressor
proving input for the given
circuit has been detected
open continuously for more
than 3 seconds during
compressor operation.
Check: All compressor
protection devices in the
associated refrigerant
circuit’s 115v contactor
control wiring circuit.
All compressors on the
associated circuit will be
locked out and prevented
from operation.
(PMR) A manual reset is
required after this
diagnostic occurs. The
Diagnostic can be reset by
the unit mounted Human
Interface Module or Tracer,
or by cycling power to the
RTM.
Condenser Pressure
Sensor Failure (Ckt-1 or
Ckt-2)
Used With: DX cooling w/
water cooled condensers.
Module: MPM
Problem: The saturated
condenser pressure sensor
input is out of range for the
given circuit.
Check: Wiring from the
MPM to the pressure
sensor. The input voltage
range should be between:
0.625 and 4.80VDC.
All compressors on the
associated circuit will be
locked out and prevented
from operation.
(PAR) An automatic reset
occurs after the Condenser
Pressure Sensor input
returns to within range for
10 continuous seconds.
Condenser Sump Heater
Failure Manual
Used With: DX cooling w/
water cooled condensers
w/sump heater.
Module: MCM
Problem: The sump min
level switch is CLOSED, and
the Sump Water
Temperature is less than
37.5 F, and has remained
this way for 20 minutes.
Check: Actual water level,
minimum level switch,
heater power circuitry.
The unit will perform Sump
Water Freeze Protection
function.
(PMR) A manual reset is
required anytime after the
Diagnostic is set to re-
enable compressor
operation. The Diagnostic
can be reset by the Human
Interface or Tracer, or by
cycling power to the RTM.
Condenser Sump Pump
Manual Fail
Used With: DX cooling w/
water cooled condensers.
Module: MCM
Problem: Sump Pump
contactor auxiliary
contacts do not close (state
change), within 6 seconds,
when the pump is
requested ON for
mechanical cooling, or are
open for 6 continuous
seconds during compressor
operation.
Check: Wiring to sump
pump, contactor, and
auxiliary contacts. Check
for pump operation.
A compressor lockout is
generated on all circuits.
(PMR) A manual reset is
required anytime after the
Diagnostic is set to re-
enable compressor
operation. The Diagnostic
can be reset by the Human
Interface or Tracer, or by
cycling power to the RTM.
Table 11: Diagnostics Troubleshooting Chart (continued)