RT-SVP07B-EN
77
SETUP Menu
DEVICE CHARACTERISTICS SETUP DEFINITIONS SCREENS
Device Characteristic Setup Definitions
Press ENTER to review or Adjust
Used With: All Units
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper
Max Stroke Time 30 Sec
Used With: Units w/OA Damper
Factory Presets: 30 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper
Min Voltage 2.0 VDC
Used With: Units w/OA Damper
Factory Presets: 2.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper
Max Voltage 10.0 VDC
Used With: Units w/OA Damper
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper
Direct/Reverse Act DIRECT ACTING
Used With: Units w/OA Damper
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Supply Fan IGV/VFD
Max Stroke Time 30 Sec
Used With: VVDC Units
Factory Preset: 30 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Supply Fan IGV/VFD Cmd
Min Voltage 0.0 VDC
Used With: VVDC Units
Factory Presets: 0 VDC
Possible Values: 0 to 10.0 VDC
Note:
If the unit is configured for a Supply Fan VFD, initial setting
should be 0.0 VDC. If the unit is configured with IGV set this value
to 2.0 VDC.
• Press Next/Previous keys to navigate.