26
RT-SVP07B-EN
STATUS Menu
The status menu is used to view various operating conditions such as temperatures, pressures and humidity levels. It is
also used to view unit component status such as fan, compressor, heater, and economizer operation, as well as setpoint
status.
The screens shown in this section are for example only. Pressing the
+
(
Plus
) key while viewing any of the status display
screens will add that screen to the Custom menu. While viewing the Custom menu, a screen can be removed by pressing
the
–
(
Minus
) key.
When a status screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general
operating status display. If this happens, press the
Status
key again to return to the status menu. The following are
examples of status screens that may be viewed by pressing the
Status
key.
Note:
1. Many of the screens displayed in this section are applicable only for the options that are installed in the unit
and may not be visible on your unit.
2. The range for some selections depend upon a sensor connected to a control module. Normal ranges
expected will be listed for each screen shown. If the sensor is operating outside its normal limits, or has
failed, “+ERR” will appear if out of range high, and “-ERR” if it is out of range low.
Press the
Status
key to begin viewing the status screens.
TOP LEVEL STATUS SCREEN
VVDA OA Flow 350.0 CCFM Supply Fan ON
Occupied Cool 4 Diagnostics
• Press Next/Previous keys to navigate.
GENERAL SYSTEM STATUS SUBMENU SCREENS
General System Status Submenu
Press ENTER to View Data in this Submenu
Used With: All Units
• Press Next key to skip this Submenu.
Active Unit Control Source: LOCAL
Active Cluster Member Role: STANDALONE
Used With: BAS Interface Installed
Possible Values:
Source: LOCAL, BAS/NETWORK
Role: STANDALONE, SLAVE, MASTER
• Press Next/Previous keys to navigate.
RTM Supply Fan Relay: OFF
RTM Supply Airflow Proving: FLOW
Used With: All Units
Possible Values:
Fan Relay: ON, OFF
Airflow Proving: FLOW, NO FLOW
• Press Next/Previous keys to navigate.
Note:
One of the three following screens will be shown based on
supply air pressure options.