42
RT-SVP07B-EN
STATUS Menu
Active Occ Dehumidification Setpt From
HI (KEYPAD) SETPOINT MENU is 60%
Used With: Units w/Dehumid. Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 40 to 65%
• Press Next/Previous keys to navigate.
Active Unocc Dehumidification Setpt From
HI (KEYPAD) SETPOINT MENU is 60%
Used With: Units w/Dehumid. Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 40 to 65%
• Press Next/Previous keys to navigate.
Active Supply Air Reheat Setpoint From
HI (KEYPAD) SETPOINT MENU is 70.0°F
Used With: Units w/Dehumid. Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 60 to 80F
• Press Next/Previous keys to navigate.
Active Occ Humidification Setpt From
HI (KEYPAD) SETPOINT MENU is 40%
Used With: Units w/Humid. Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 20 to 50%
• Press Next/Previous keys to navigate.
Active Unocc Humidification Setpt From
HI (KEYPAD) SETPOINT MENU is 20%
Used With: Units w/Humid. Option
Possible Values:
HI (KEYPAD) SETPOINT MENU
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 20 to 50%
• Press Next/Previous keys to navigate.