RT-SVP07B-EN
145
DIAGNOSTICS Menu
Ventilation Control
Module (VCM)
• Front Velocity
Pressure Transducer
• Back Velocity
Pressure Transducer
• Auxiliary
Temperature
• Space CO
2
Sensor
• Outside Air CFM
(PCB Only)
• None • Preheater
Relay
• Pressure Calibration
Ventilation
Override Module
(VOM)
• None
• VOM Mode A
Contacts
• VOM Mode B
Contacts
• VOM Mode C
Contacts
• VOM Mode D
Contacts
• VOM Mode E
Contacts
• VOM Relay
Generic BAS
Module 5V (GBAS5)
• Configuration
Module
• Analog Input 1
• Analog Input 2
• Analog Input 3
• Analog Input 4
Note:
1. Each of these
inputs can be
configured as defined
in GBAS(5VDC) input
assignments.
2. No 2 inputs can be
assigned to the same
definition.
3. The min voltage
(0.5vdc) is associated
with the min range of
the assigned setpoint.
4. The max voltage
(4.5vdc) is associated
with the max range of
the assigned setpoint.
• None
• Binary Input 1
Note: This input is
designated as the
GBAS5 Demand Limit
Input
• Binary Output 1
• Binary Output 2
• Binary Output 3
• Binary Output 4
• Binary Output 5
Note: These outputs,
when energized,
indicated the
diagnostic(s) assigned
to them under GBAS5
output assignments
are active.
Table 12. Module I/O Descriptions (continued)