76
RT-SVP07B-EN
SETUP Menu
Temperature Input Calibration Screens
The following five (5) Offset screens are used only if calibration of a sensor designated to perform the listed function is
necessary.
Example: If the temperature sensor for Morning Warm Up (MWU) is checked and a difference between the actual
measured room temperature and the corresponding measured sensor value is found, by programming the amount of
error into the Temperature Input Offset for Morning Warm Up (MWU) Heat — The sensor can be calibrated.
CALIBRATION AND OFFSET SUBMENU SCREENS
Calibration and Offset Submenu
Press ENTER to Review or Adjust
Used With: All Units
• Press the Next key to skip this Submenu.
Temperature Calibration Offset For
RTM Zone Temperature Input 0.0°F
Used With: All Units
Factory Presets: 0.0ºF
Possible Values: -5.0 to 5.0ºF
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For
RTM Aux Temperature Input 0.0°F
Used With: All Units
Factory Presets: 0.0ºF
Possible Values: -5.0 to 5.0ºF
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For
RTM Outside Air Temperature Input 0.0°F
Used With: All Units
Factory Presets: 0.0ºF
Possible Values: -5.0 to 5.0ºF
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For
Heat Module Aux Temp Input 0.0°F
Used With: Units w/Heat or Chilled
Water Installed
Factory Presets: 0.0ºF
Possible Values: -5.0 to 5.0ºF
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For
ECEM Return Air Temperature Input 0.0°F
Used With: Units w/Comparative
Enthalpy Installed
Factory Presets: 0.0ºF
Possible Values: -5.0 to 5.0ºF
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.