74
RT-SVP07B-EN
SETUP Menu
Assign Diagnostic to Alarm Output 1?
RTM Zone Temp Sensor Failure (Yes)
Used With: Units w/GBAS(10VDC)
Selecting “Yes” for each of the diagnostics displayed will activate the
associated Alarm Output when that diagnostic is activated.
Note:
The list of diagnostics displayed here will be dependent upon
the module assignments selected. See the “Diagnostics Table” in the
diagnostics menu section for the complete list displayed for each
module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter GBAS
• Press Next/Previous keys to navigate.
GBAS
(0-10
VDC)
Analog
Output
1
Assignment
NOT ASSIGNED
Used With: Units w/GBAS(10VDC)
Installed
Factory Presets: NOT ASSIGNED
Possible Values:
NOT ASSIGNED
ACTIVE COOLING CAPACITY
ACTIVE HEATING CAPACITY
OUTSIDE AIR TEMPERATURE
ACTIVE ZONE TEMPERATURE
ACTIVE SUPPLY AIR TEMPERATURE
ACTIVE SUPPLY AIR PRESSURE
ACTIVE SPACE PRESSURE
ACTIVE SPACE RELATIVE HUMIDITY
ACTIVE OUTDOOR AIR HUMIDITY
ACTIVE SPACE CO
2
LEVEL
ACTIVE OA DAMPER POSITION
ACTIVE OUTDOOR AIR FLOW
Note:
There are 3 additional screens associated with Output
Assignments; “Analog Output 2”, “Analog Output 3”, and “Analog
Output 4”. Press the Next key to proceed through the remaining
assignments.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to enter SETUP
• Press Next/Previous keys to navigate.