RT-SVP07B-EN
79
SETUP Menu
Actuator Setup Exhaust Damper/VFD
Max Voltage 10.0 VDC
Used With: Units w/Power Exhaust
Factory Presets: 10.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD
Direct/Reverse Act DIRECT ACTING
Used With: Units w/Power Exhaust
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic
Max Stroke Time 60 Sec
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: 60 Sec
Possible Values: 1 to 255 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic
Min Voltage 2.0 VDC
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: 2.0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic
Max Voltage 10.0 VDC
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: 0 VDC
Possible Values: 0 to 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic
Direct/Reverse Act DIRECT ACTING
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING,
REVERSE ACTING
• Press Next/Previous keys to navigate.
Note:
Only one of the following two screens will be shown
Actuator Setup Num 1 Low Ambient
Max Stroke Time 60 Sec
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 60 Sec
Possible Values: 1 to 255 Sec
OR
Actuator Setup Cond Fan VFD Ckt 1
Max Stroke Time 60 Sec
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 60 Sec
Possible Values: 1 to 255 Sec
Press the Next key to navigate forward.