RT-SVP07B-EN
27
STATUS Menu
Supply Fan IGV/VFD Target: 30%
Master’s Algorithm Command to All Units
Used With: Clustered VVDA Units
Possible Values: 0 to 100%
OR
Supply Fan IGV/VFD Cmd Opening To 30 %
Active Supply Air Pressure 2.0 IWC
Used With: VVDA Units
Possible Values:
Cmd: 0 to 100%
Press: 0.0 to 7.9 IWC
“Opening To” and ”Closing To” indicate direction.
“Limited To” when shown indicates an active override.
OR
Active Supply Air Pressure 2.0 IWC
Used With: CVDA/CVZT Units
Possible Values: 0.0 to 7.9 IWC
• Press Next/Previous keys to navigate.
Note:
One of the three following screens will be shown based on
power exhaust options.
Exhaust Fan OFF
Used With: Units w Power Exhaust w/o
Statitrac, w/o Return Fan
Possible Values: ON, OFF
OR
Exhaust Damper/VFD Target: 70 %
Master’s Algorithm Command to All Units
Used With: Clustered, w/Statitrac, w/o
Return Fan Units
Possible Values: 0 to 100%
OR
Exhaust Fan ON Space Pressure 0.00 IWC
Exhaust Damper/VFD Opening To 32 %
Used With: Units w/Statitrac, w/o
Return Fan
Possible Values:
Fan: ON, OFF
Pressure:
IPakI: -0.2 to 0.3 IWC
IPakII: -0.67 to 0.67 IWC
Damper/VFD: 0 to 100%
“Opening To” and ”Closing To” indicates direction.
“Limited To” when shown indicates an active override.
• Press Next/Previous keys to navigate.
Note:
One of the four following screens will be shown based on
heating type options.