RT-SVP07B-EN
41
STATUS Menu
Active Occupied Zone Heating STP From
HI (KEYPAD) SETPOINT MENU is 71°F
Used With: CVZT w/Heat, VV/CVDA w/
DWU or MWU Installed
Possible Values:
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 50 to 88ºF
• Press Next/Previous keys to navigate.
Active Unoccupied Zone Cooling STP From
HI (KEYPAD) SETPOINT MENU is 85°F
Used With: All Units
Possible Values:
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 52 to 90ºF
• Press Next/Previous keys to navigate.
Active Unoccupied Zone Heating STP From
HI (KEYPAD) SETPOINT MENU is 60°F
Used With: Units w/Heat Installed
Possible Values:
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 50 to 88ºF
• Press Next/Previous keys to navigate.
Active Morning Warmup Setpoint From
HI (KEYPAD) SETPOINT MENU is 72°F
Used With: Units w/MWU ENABLED
Possible Values:
HI (KEYPAD) SETPOINT MENU
ZONE SENSOR SETPOINT INPUT
NSB PANEL SETPOINT INPUT
GBAS 0-5 VDC MODULE
GBAS 0-10 VDC MODULE
BAS/NETWORK
Range: 52 to 90ºF
• Press Next/Previous keys to navigate.
Active Rapid Restart Critical Stpt From
HI (KEYPAD) SETPOINT MENU is 90°F
Used With: Units w/Rapid Restart
Possible Values:
HI (KEYPAD) SETPOINT MENU
Range: 75 to 95ºF
• Press Next/Previous keys to navigate.