RT-SVP07B-EN
33
STATUS Menu
Circuit 2 Cond Fan Staging
K5: ON
K6: ON
Stage 4
Used With: DX Cooling > 40Ton
Possible Values:
K5: ON, OFF; K6: ON, OFF
Bottom Right Field:
OFF
Stage 1
Stage 2
Stage 3
Stage 4
“K6:” status not displayed and maximum stage is 1 on water-
cooled condenser units.
• Press Next/Previous keys to navigate.
Condenser Fan Speed:
Circuit 1: 100% Circuit 2: 100%
Used With: DX Cooling w/Low Ambient
Option or Water-Cooled Condensers
Possible Values:
Circuit 1: 0 to 100%
Circuit 2: 0 to 100%
“Circuit 2:” only shown for units > 40Tons.
• Press Next/Previous keys to navigate.
Condenser Sump Water Temp: 73.1°F
Condenser Sump Heater Relay: OFF
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values:
Temp: 0.0 to 200.0ºF
Relay: ON, OFF
“Cond Sump Heater Relay” only shown if Sump Heater installed.
• Press Next/Previous keys to navigate.
Condenser Sump Pump Relay Command: ON
Condenser Sump Pump Proving: FLOW
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values:
Relay: ON, OFF
Proving: FLOW, NO FLOW
• Press Next/Previous keys to navigate.
Condenser Sump Fill Relay: OFF
Condenser Sump Fill Valve: OPEN
Used With: DX Cooling w/Water-Cooled
Condensers
Possible Values:
Relay: ON, OFF
Valve: CLOSED, OPEN
• Press Next/Previous keys to navigate.