SETUP Menu
After the unit is installed, the control modules must be programmed with certain setup information in order to operate
and function properly. The data necessary for unit operation will vary depending on certain factors such as unit size, type,
and installed options.
The setup menu is used to input initial operating information such as control parameters, setpoint source selection, sensor
source selections, ventilation override definitions, functions enable/disable, text display (Language), units displayed
(English or SI), unit diagnostic assignments, and system tuning parameters. When a setup screen is displayed for 30
minutes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press
the
Setup
key again to return to the setup menu.
Information that pertains to when the screens are shown, the possible values that may be designated, and the factory
presets for these values is located to the right of each programmable screen.
Note:
1. Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may
not be visible on your unit.
2. If a screen is not visible on the Unit Human Interface Module, refer to the “Used With” information listed to the right
of each screen in this book.
Modifying Selections:
Starting with the first setup screen program the necessary information by using the
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has been
changed to the desired value, the user has the following options to either
Cancel
or
Accept
the pending change:
•
To
Cancel
, press the
Cancel
key to remove the change, the display will revert to the original value.
•
To
Accept
, press the
Enter
key to confirm the new choice.
Press the
Setup
key to begin viewing or modifying the setup screens.
TOP LEVEL SETUP SCREEN
Display Text in: ENGLISH LANGUAGE
Display Units Using: ENGLISH NOTATION
Used With: All Units
Factory Presets:
Text Language: ENGLISH
Units Notation: ENGLISH
Possible Values:
Language: ENGLISH, FRENCH,
SPANISH
Notation: ENGLISH, SI
• Press Next/Previous keys to navigate.
GENERAL UNIT FUNCTIONS SETUP SUBMENU SCREENS
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
Used With: All Units
• Press the Next key to skip this Submenu.