88
RT-SVP07B-EN
SETPOINT Menu
Humidify if Space Humidity Below
Occ Humidification Setpoint: 30%
Used With: Units w/Humidification
Option
Factory Preset: 30 %
Possible Values: 20 to 50 %
• Press Next/Previous keys to navigate.
Stop Humid if Space RH Above STP Plus
Occ Humid Hysteresis Offset: 5%
Used With: Units w/Humidification
Option
Factory Preset: 5 %
Possible Values: 3 to 10 %
• Press Next/Previous keys to navigate.
Humidify if Space Humidity Below
Unocc Humidification SETPOINT: 30%
Used With: Units w/Humidification
Option and Unocc. Humid. Enabled
Factory Preset: 30 %
Possible Values: 20 to 50 %
• Press Next/Previous keys to navigate.
Stop Humid if Space RH Above STP Plus
Unocc Humid Hysteresis Offset: 5%
Used With: Units w/Humidification
Option and Unocc. Humid. Enabled
Factory Preset: 5 %
Possible Values: 3 to 10 %
• Press Next/Previous keys to navigate.
End Of Submenu (NEXT) to Enter SETPOINT
• Press Next/Previous keys to navigate.
OUTSIDE AIR CONTROL SETPOINT SUBMENU SCREENS
Outside Air Control Setpoint Submenu
Press ENTER to Review or Adjust
Used With: Units w/Fresh Air Option
• Press the Next key to skip this Submenu.
When Economizer Cooling, Reduce Zone
Temperature Cooling Setpoint By: 1.5°F
Used With: CVZT Units w/Economizer
Option
Factory Preset: 1.5ºF
Possible Values: 0.0 to 3.0ºF
• Press Next/Previous keys to navigate.