3.9.4 Function block No. 22: Input 2 (
2. InP
)
No.
Symbol
Name
Data range
Factory
set value
User
set value
Fn22
Function block No. 22
1)
This is the first parameter symbol of
Function block No. 22
159
2. I N P
Input 2_Input type
1)
0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PLII
10: TC input U
11: TC input L
12: TC input PR40-20
13: RTD input Pt100
14: RTD input JPt100
15: Current input 0 to 20 mA DC
16: Current input 4 to 20 mA DC
17: Voltage input 0 to 10 V DC
18: Voltage input 0 to 5 V DC
19: Voltage input 1 to 5 V DC
20: Voltage input 0 to 1 V DC
21: Voltage input
10 to
10 V DC
22: Voltage input
5 to
5 V DC
23: Voltage input 0 to 100 mV DC
24: Voltage input 0 to 10 mV DC
・
When Remote setting input is selected
and MC-(V)COS(R) pressure control is
selected for Input 1_Control action: 15 to
24
・
When Measured input 2 is selected and
MC-(V)COS(R) pressure control is
selected for Input 2_Control action: 15 to
24
Same as
Input 1_
Input type
When
Remote
setting input
is specified
at the time
of order, but
the input
type is not
specified:
17
160
2.U N I T
Input 2_Display unit
1) 2) 3)
0:
C
1:
F
Same as
Input 1_
Display unit
161
2.P G D P
Input 2_Decimal point
position
1) 3)
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
W5Re/W26Re, PR40-20: 0 (fixed)
Thermocouples other than those shown
above: 0 to 1
RTD input: 0 to 2
Voltage (V)/Current (I) input: 0 to 4
Same as
Input 1_
Decimal
point
position
162
2.P G S H
Input 2_Input range high
1)
TC/RTD inputs and Voltage (V)/Current (I)
Inputs (For other than Remote setting input):
(Input 2_Input range low + 1 digit) to Input
2_Maximum value of input range
Voltage (V)/Current (I) Inputs (For Remote
setting input):
(Input 2_Input range low + 1 digit)
to Input 1_Maximum value of input range
[Varies with the setting of the Decimal point
position.]
When 3 to 7 (pressure control operation
[MC-(V)COS(R)]) is set to Input 2_Control
action, the set value for the parameter
should be entered with the same pressure
unit selected for Input 1_Valve coefficient F.
Same as
Input 1_
Input range
high
163
2.P G S L
Input 2_Input range low
1)
TC/RTD inputs and Voltage (V)/Current (I)
Inputs (For other than Remote setting input):
Input 2_Minimum value of input range to
(Input 2_Input range high - 1 digit)
Voltage (V)/Current (I) Inputs (For Remote
setting input):
Input 1_Minimum value of input range to
(Input 2_Input range high - 1 digit)
Same as
Input 1_
Input range
low
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...