172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
116
Switching between Direct/Reverse action is available, only while the instrument
is at STOP. Switching is not available during RUN. Setting the contact at RUN
beforehand will perform switching when the instrument enters the STOP mode.
If “Input 1_Control action” or “Input 2_Control action” is set to “0: PID control
with Autotuning
(direct action)” or “1: PID control with Autotuning (reverse
action),” PID action is switched between reverse and direction actions.
The above open/close action can be reversed (reversing the functions of open and
close). Can be set in Function block No. 23: DI logic invert (Engineering mode).
Timing chart of functions
RUN/STOP
STOP
RUN
STOP
RUN
STOP
Auto/Manual
Manual
Auto
Manual
Auto
Manual
Remote/Local
Local
Remote
Local
Remote
Local
PV select transfer
Input 1
Input 2
Input 1
Input 2
Input 1
2-loop/Differential
temperature
2-loop control
Differential
temp. control
2-loop control
Differential
temp. control
2-loop control
Cascade
Slave/Master
single
Cascade
Slave/Master
single
Cascade
Slave/Master
single
Unlock/lock
Unlock
Lock
Unlock
Lock
Unlock
Direct/Reverse
action
Reverse action
Direct action
Reverse action
Direct action
Reverse action
After the contact is transferred, it takes “up to 200 ms” until the action of
this instrument is actually selected.
●
Interlock release, Peak/Bottom hold release
Through the detection of close edge (rising edge), Interlock state and Peak (or
Bottom) hold values are released.
Timing chart for releasing interlock, peak and bottom hold
Interlock
Interlock state
Interlock release
Peak/Bottom hold
Peak/Bottom hold state
Peak/Bottom hold release
After the contact is transferred, it takes “up to 200 ms” until the action of
this instrument is actually selected.
Contact closed
Contact open
Up to 200 ms
NOTE
Contact closed
Contact open
Up to 200 ms
Close edge
NOTE
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...