172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
285
Transfer timing of Remote/Local
(Cascade control/Single control)
After the contact is transferred, it takes “up to 200 ms” until the action of
this instrument is actually selected.
The above switching action can be inverted (The functions at contact close and
contact open can be swapped). This setting can be done at “DI logic invert.”
Refer to 5.2 Switching Functions Using Digital Inputs (DI) for details.
Remote/Local transfer (Cascade control) state
The table below shows the actual Cascade control/Single control status and displays
under different combinations of settings by Key operation, Communication, and
Digital input (DI).
Setting via front keys
or through
communication
Setting via Digital Input
(DI)
Instrument status
Cascade control
Cascade control
Cascade control
Single control
(Master/Slave)
Single control
(Master/Slave)
Single control
(Master/Slave)
Cascade control
Single control
(Master/Slave)
Parameter setting
Remote/Local transfer (Cascade control) [Operation Transfer Mode]
Parameter symbol
Data range
Factory set value
R/ L
When “Cascade control” is selected at Select function for input 2
SNGL
: Single control (Master single or Slave single)
CAS
: Cascade control
SNGL
To display “Remote/Local transfer” (Cascade control), choose “Cascade control”
in Function block No. 58: Select function for Input 2 (Engineering mode).
Input 1_Proportional band [heat-side] [Parameter Setting Mode: Parameter
group No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1.
U
1
P
TC/RTD inputs:
0 (0.0, 0.00) to Input 1_Input span (Unit:
C [
F])
(When Control with PV select: 0 to PV select input span)
[Varies with the setting of the Decimal point position.]
Voltage (V)/Current (I) inputs:
0.0 to 1000.0% of Input 1_Input span
(When Control with PV select: 0.0 to 1000.0% of PV select
input span)
0 (0.0, 0.00): ON/OFF action
NOTE: 0 (0.0, 0.00) cannot be set when a setting
“Temperature control operation [MC-(V)COS(R)] is
selected in Input 1_control action.
TC/RTD inputs: 30
V/I inputs: 3.0
To display
“Input 1_Proportional band [heat-side]”, choose a setting other than
“3 to 7 (Pressure control operation [MC-(V)COS(R)])” in Function block No.51:
Input 1_Control action (Engineering mode).
Local
Local
Local
Remote
Remote/Local
Up to 200 ms
Contact closed
Contact open
Remote
NOTE
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...