172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
51
3.8.6 Setting group No. 52: Input 2_Control (
2.ConT
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Sn52
Setting group No. 52
This is the first parameter symbol of
Setting group No. 52
100
2. M.M V
Input 2_Manual
manipulated output value
1)
Input 2_Output limiter low to Input 2_
Output limiter high
Pressure/temperature control operation
[MC-(V)COS(R)]:
Input 2_Output limiter low to whichever
the smaller value of either "calculated
value from Input 2_Pressure
(temperature) limiter" or "Input 2_Output
limiter high [heat-side]. When STOP is
set, Input 2_Output limiter low [heat-side]
to Input 2_Output limiter high [heat-side]
-5.0
101
2.LEV1
Input 2_Level PID setting
1
2) 3)
Input 2_Input range low to Input 2_Input
range high
[Varies with the setting of the Decimal
point position.]
Input 2_
Input
range high
102
2.LEV2
Input 2_Level PID setting
2
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
103
2.LEV3
Input 2_Level PID setting
3
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
104
2.LEV4
Input 2_Level PID setting
4
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
105
2.LEV5
Input 2_Level PID setting
5
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
106
2.LEV6
Input 2_Level PID setting
6
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
107
2.LEV7
Input 2_Level PID setting
7
2) 3)
Same as Input 2_Level PID setting 1
Same as
Input 2_
Level PID
setting 1
1)
Displayed when "2-loop control/Differential temperature control" is selected in "Select function for Input 2."
2)
Displayed when Input 2 is with Level-PID AND "2-loop control/Differential temperature control" is selected in Select function for Input
2, AND a setting other than "Pressure control operation [MC-(V)COS(R)]" is selected for "Input 2_Control action".
3)
Input 2_Level PID settings 1 to 7 always maintain the following relation.
(Input 2_Level PID setting 1) less than or equal to (Input 2_Level PID setting 2) less than or equal to (Input 2_Level PID setting 3)
less than or equal to (Input 2_Level PID setting 4) less than or equal to (Input 2_Level PID setting 5) less than or equal to (Input
2_Level PID setting 6) less than or equal to (Input 2_Level PID setting 7)
3.8.7 Setting group No. 53: Input 1_Tuning (
1.TUNE
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Sn53
Setting group No. 53
1)
This is the first parameter symbol of
Setting group No. 53
108
1. ATb
Input 1_AT bias
1)
-(Input 1_Input span) to +(Input 1_Input
span)
(When Control with PV select:
-(PV select input span) to +(PV select
input span))
[Varies with the setting of the Decimal
point position.]
0
109
1.ATTM
Input 1_AT remaining
time monitor
1)
0 hours 00 minutes to 48 hours 00
minutes
110
1.TUNE
Input 1_AT/ST status
monitor
1)
0: AT/ST complete
1: AT running now
2: ST running now
-1: Aborted. Setting changed
-2: Aborted. Abnormal input
-3: Aborted. Timeout
-4: Aborted. Abnormal calculated values
1)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 1_Control action".
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...