172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
125
●
When setting PV bias and PV ratio at the same time
[Example]
When PV bias = 15
C and
Measured value (PV) = 50
C
If PV ratio = 0.700
Displayed value = 50
0.700 + 15 = 50
C
PV ratio = 1.500
Displayed value = 50
1.500 + 15 = 90
C
Parameter setting
●
Input 1_PV bias [Setup Setting Mode: Setting group No. 21 (
Sn21
)]
Parameter symbol
Data range
Factory set value
1. P b
- (Input 1_Input span) to +(Input 1_Input span)
(When Control with PV select:
- (PV select input span) to +( PV select input span))
[Varies with the setting of the Decimal point position.]
0
●
Input 2_PV bias (RS bias) [Setup Setting Mode: Setting group No. 22 (
Sn22
)]
Parameter symbol
Data range
Factory set value
2. Pb
Input 2_PV bias
- (Input 2_Input span) to +(Input 2_Input span)
RS bias
- (Input 1_Input span) to +(Input 1_Input span)
[Varies with the setting of the Decimal point position.]
0
When Remote setting input is supplied, it is displayed as RS bias.
Input 2_Input type is not displayed when
“No function” is selected in Function
block No. 58: Select function for Input 2 (Engineering mode).
●
Input 1_PV ratio [Setup Setting Mode: Setting group No. 21 (
Sn21
)]
Parameter symbol
Data range
Factory set value
1. PR
0.500 to 1.500
1.000
●
Input 2_PV ratio [Setup Setting Mode: Setting group No. 22 (
Sn22
)]
Parameter symbol
Data range
Factory set value
2. P R
Input 2_PV ratio: 0.500 to 1.500
RS ratio: 0.001 to 9.999
1.000
When Remote setting input is supplied, it is displayed as PV ratio.
Input 2_Input type is not displayed when
“No function” is selected in Function
block No. 58: Select function for Input 2 (Engineering mode).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...