172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
254
Input 1_Integral time [heat-side] [Parameter Setting Mode: Parameter group
No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1.
I
0 to 3600 seconds, 0.0 to 3600.0 seconds or 0.00 to 360.00
seconds
0 (0.0, 0.00): PD action
[Varies with the setting of the Integral/Derivative time decimal
point position.]
240
To display “Input 1_Integral time [heat-side]”, choose a setting other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.51: Input 1_
Control action (Engineering mode). Additionally, a value other than 0 must also
be entered in the Input 1_Proportional band in the same memory area.
Input 1_Derivative time [heat-side] [Parameter Setting Mode: Parameter
group No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1.
d
1 to 3600 seconds, 0.0 to 3600.0 seconds or 0.00 to 360.00
seconds
0 (0.0, 0.00): PI action
[Varies with the setting of the Integral/Derivative time decimal
point position.]
60
To display
“Input 1_Deriative time [heat-side]”, choose a setting other than “3 to
7 (Pressure control operation [MC-
(V)COS(R)])” in Function block No.51: Input
1_Control action (Engineering mode). Additionally, a value other than 0 must
also be entered in the Input 1_Proportional band in the same memory area.
Input 1_Control response parameter [Parameter Setting Mode: Parameter
group No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1. RP T
0: Slow
1: Medium
2: Fast
[When P or PD action is selected, this setting will be
unavailable]
PID control: 0
Heating/Cooling PID
control: 2
To display “Input 1_Control response parameter”, choose a setting other than “3
to 7 (Pressure control operation [MC-
(V)COS(R)])” in Function block No.51:
Input 1_Control action (Engineering mode).
Input 2_ Proportional band [Parameter Setting Mode: Parameter group No.
52 (
Pn52
)]
Parameter symbol
Data range
Factory set value
2.
P
TC/RTD inputs: 0 (0.0, 0.00) to Input 2_Input span
(Unit:
C [
F])
(2When Control with PV select: 0 to PV select input span)
[Varies with the setting of the Decimal point position.]
Voltage (V)/Current (I) Input: 0.0 to 1000.0 % of Input 1_Input
span
(2When Control with PV select:: 0.0 to 1000.0 % of PV select
input span)
0 (0.0, 0.00): ON/OFF action
NOTE: 0 (0.0, 0.00) cannot be set when a setting
“Temperature control operation [MC-(V)COS(R)] is
selected in Input 2_control action.
TC/RTD inputs: 30
V/I inputs: 3.0
To display “Input 2_Proportional band”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2 (Engineering mode), AND choose a setting other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input 2_
Control action (Engineering mode).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...