172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
255
Input 2_Integral time [Parameter Setting Mode: Parameter group No. 52
(
Pn52
)]
Parameter symbol
Data range
Factory set value
2.
I
0 to 3600 seconds, 0.0 to 3600.0 seconds or 0.00 to 360.00
seconds
0 (0.0, 0.00): PD action
[Varies with the setting of the Integral/Derivative time decimal
point position.]
240
To display “Input 2_Integral time”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2 (Engineering
mode), AND choose a setting other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input
2_Control action (Engineering mode). Additionally, a value other than 0 must
also be entered in the Input 2_Proportional band in the same memory area.
Input 2_Derivative time [Parameter Setting Mode: Parameter group No. 52
(
Pn52
)]
Parameter symbol
Data range
Factory set value
2.
d
1 to 3600 seconds, 0.0 to 3600.0 seconds or 0.00 to 360.00
seconds
0 (0.0, 0.00): PI action
[Varies with the setting of the Integral/Derivative time decimal
point position.]
60
To display “Input 2_Derivative time”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2
(Engineering mode), AND choose a setting other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input
2_Control action (Engineering mode). Additionally, a value other than 0 must
also be entered in the Input 2_Proportional band in the same memory area.
Input 2_Control response parameter [Parameter Setting Mode: Parameter
group No. 52 (
Pn52
)]
Parameter symbol
Data range
Factory set value
2. RP T
0: Slow
1: Medium
2: Fast
[When P or PD action is selected, this setting will be
unavailable]
0
To display “Input 2_Control response parameter”, choose “2-loop control/
Differential temperature control” or “Cascade control” in Function block No. 58:
Select function for Input 2 (Engineering mode), AND choose a setting other than
“3 to 7 (Pressure control operation [MC-VCOS(R)])” in Function block No. 52:
Input 2_Control action (Engineering mode).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...