Re-hold action
When Re-hold action is ON, the event action is also suppressed at the Set value (SV)
change until the Measured value (PV) has entered the non-event range.
Action condition
Hold action
Re-hold action
When the power is turned on
Works
Works
When transferred from STOP (control
STOP) to RUN (control RUN)
Works
Works
When the Set value (SV) is changed
Does not work
Works
[Example] When Event 1 type is the deviation low:
When re-hold action is OFF and event output type is deviation, the event output is
produced due to the Set value (SV) change. The re-hold action suppresses the alarm
output until the measured value has entered the non-event range again.
When high alarm with hold action/re-hold action is used for Event function,
alarm does not turn on while hold action is in operation. Take measures to
prevent overheating which may occur if the control device fails.
The re-hold action will be unavailable for any of the following.
Setting of Soft start or Setting change rate limiter is other than
“0 (no function)”
Remote mode
Cascade control
Differential temperature control
Parameter setting
Event 1 hold action [Engineering Mode: Function block No. 41 (
Fn41
)]
Parameter symbol
Data range
Factory set value
EH O 1
0: Hold action OFF
1: Hold action ON
2: Re-hold action ON
Setting hold or re-hold action on the event that is not available
with hold and re-hold actions will just be ignored.
0
Event 2 hold action [Engineering Mode: Function block No. 42 (
Fn42
)]
Parameter symbol
Data range
Factory set value
EH O 2
0: Hold action OFF
1: Hold action ON
2: Re-hold action ON
Setting hold or re-hold action on the event that is not available
with hold and re-hold actions will just be ignored.
0
Set value
Event set value
Measured value (PV)
Set value
Event set value
Measured value (PV)
Before the change of
set value
After the change of
set value
The change of set value
Event area
Event area
NOTE
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...