172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
234
Input 1_Overlap/Deadband [Parameter Setting Mode: Parameter group No.
56 (
Pn56
)]
Parameter symbol
Data range
Factory set value
1.
U
d b
TC/RTD inputs:
-(Input 1_Input span)to +(Input 1_Input span)
(When Control with PV select:
-(PV select input span) to +(PV select input span))
(Unit:
C [
F])
[Varies with the setting of the Decimal point position.]
Voltage (V)/Current (I) inputs:
-100.0 to +100.0% of Input 1_Input span
(When Control with PV select:
-100.0 to +100.0% of PV select input span)
Minus (-) setting results in Overlap. However, the overlapping
range is within the proportional range.
TC/RTD inputs: 0
V/I inputs: 0.0
To display “Input 1_Overlap/Deadband”, choose “Heating/Cooling PID control”
in Function block No.51: Input 1_Control action (Engineering mode).
Input 1_Control action [Engineering Mode: Function block No. 51 (
Fn51
)]
Parameter symbol
Data range
Factory set value
1. O S
0: PID control with Autotuning (direct action)
1: PID control with Autotuning (reverse action)
2: Heating/Cooling PID control with Autotuning [Cooling linear
type]
3: Pressure control operation [MC-COS(R)-3]
4: Pressure control operation [MC-COS(R)-16, 15 to 50 mm]
5: Pressure control operation [MC-COS(R)-16, 65 to 150 mm]
6: Pressure control operation [MC-COS(R)-21]
7: Pressure control operation [MC-VCOS(R)]
8: Temperature control operation [MC-COS(R)-16]
9: Temperature control operation [MC-VCOS(R)]
For cascade control, only 0 or 1 are selectable.
For PV select, only 0, 1 or 2 are selectable.
Product identification code
specified at the time of
order.
Refer to “4. Parameters that are Initialized/Modified when Setting is Changed” for
the parameters that are initialized when the Input 1_Control action is changed.
Undershoot suppression factor [Engineering Mode: Function block No. 56
(
Fn56
)]
Parameter symbol
Data range
Factory set value
U S
0.000 to 1.000
1.000
To display “Undershoot suppression factor”, choose “Heating/Cooling PID
control” in Function block No.51: Input 1_Control action (Engineering mode).
Overlap/Deadband reference point [Engineering Mode: Function block No.
56 (
Fn56
)]
Parameter symbol
Data range
Factory set value
U
d B PA
0.0 to 1.0
0.0
To display “Overlap/Deadband reference point”, choose “Heating/Cooling PID
control” in Function block No.51: Input 1_Control action (Engineering mode).
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...