172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
252
Input 2_Valve coefficient F [Engineering Mode: Function block No. 54 (
Fn54
)]
Parameter symbol
Data range
Factory set value
2. F
When Input 2_Control action is set to 3 to 6 or 8:
0: kg/cm
2
G
1: barg
2: psig
3: kPaG
4: MPaG
When Input 2_Control action is set to 7 or 9:
10: mmHg/Torr
11: mbar
12: inHg
13: psi
14: kPa
NOTE: The pressure unit to be entered for the pressure value
is defined by the valve coefficient F. To use a pressure unit
other than the valve coefficient F (indicated on the valve
coefficient plate), refer to the "Converting valve coefficient"
section to convert the valve coefficient and change the valve
coefficient F along with valve coefficients A, C, and E.
Same as Input 1_Valve
coefficient F
Valve coefficient value (A to F) is indicated in the valve coefficient plate
(attached) on the MC-(V)COS(R), which is also indicated on the valve
coefficient tag when the equipment is new.
To display “Input 2_Valve coefficient F”, choose “2-loop control/Differential
temperature control” in Function block No. 58: Select function for Input 2
(Engineering mode), AND choose “3 to 7 (Pressure control operation [MC-
(V)COS(R)])” or “8 and 9 (Temperature control operation [MC-(V)COS(R)])” in
Function block No.52: Input 2_Control action (Engineering mode).
Input 2_Pressure (temp) limiter [Engineering Mode: Function block No. 54
(
Fn54
)]
Parameter symbol
Data range
Factory set value
2. Pr L
When Input 2_Control action is set to 3 to 7:
Input 1_Input range low to Input 2_Input range high
When Input 2_Control action is set to 8:
Valve coefficient
Coefficient F = 0 (kg/cm
2
G): 0.00 to 99.99
Coefficient F = 1 (barg) 0.00 to 99.99
Coefficient F = 2 (psig) 0.0 to 999.9
Coefficient F = 3 (kPaG): 0 to 9999
Coefficient F = 4 (MPaG) 0.000 to 9.999
When Input 2_Control action is set to 9:
The smaller value of 0.0 to Input 1_Input range high or
140.0 °C (280.0 °F)
Select the temperature unit according to the following
conditions:
When Input type is set to Temperature input: Input 2
Display unit
When Input type is set to V/I input: Input 2_Temperature
limiter unit
When 0 (0.0, 0.00, 0.000) and Input 2_Pressure (Temp)
Limiter function OFF
[Varies with the setting of the Decimal point position when Input
2_Control action is a setting other than
“8”.]
Input 2_Control action is a
setting other than 7: 0
Input 2_Control action is set
to 7: Input 2_Input range
high
To display “Input 2_Pressure (Temperature) limiter”, choose “2-loop control/
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...