172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
374
When the SV tracking function is selected at the time of switching from
Manual to Auto mode, the Set value (SV) of the Memory area will be ignored.
Refer to 6.8 Suppressing Sudden Change in Output (Balanceless
Bumpless) for Bumpless action at the time of switching between
Auto/Manual, .
Refer to 8.17 Continuing Stable Control after the Operation Transfer (SV
Tracking) for the SV tracking function.
Manipulated output value (Area):
When either “Auto mode (bump)” or “Manual mode
(bump)” is selected in the Auto/Manual transfer selection (Area), the Manipulated
output value just after the switching is complete needs to be set here.
Remote/Local transfer selection (Area): Select the Operation mode at the time of
Memory area switching. The operation mode depends on the action selected in
Select function for input 2.
Remote setting input: Remote mode/Local mode switching
Cascade control: Cascade control/Single control switching
Control with PV select: Input 1/Input 2 switching
2-loop control/Differential temperature control: 2-loop control/Differential
temperature control switching
When the SV tracking function is selected at the time of the operation mode
transfer, the operation mode follows the action set in the SV tracking.
Refer to 8.17 Continuing Stable Control after the Operation Transfer (SV
Tracking) for the SV tracking function.
Besides the above, the Setting change rate limiter unit time and Area soak time
unit are set in the Engineering mode
Example: Operating a simple sequence using Memory areas 1 through 4
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...