172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
70
3.9.17 Function block No. 52: Input 2_Control (
2.ConT
)
No.
Symbol
Name
Data range
Factory
set value
User
set value
Fn52
Function block No. 52
1)
This is the first parameter symbol of
Function block No. 52
248
2. OS
Input 2_Control action
1)
0: PID control with Autotuning (direct action)
1: PID control with Autotuning (reverse
action)
3: Pressure control operation [MC-COS(R)-3]
4: Pressure control operation [MC-COS(R)-
16, 15 to 50 mm]
5: Pressure control operation [MC-COS(R)-
16, 65 to 150 mm]
6: Pressure control operation [MC-COS(R)-
21]
7: Pressure control operation [MC-VCOS(R)]
8: Temperature control operation [MC-
COS(R)-16]
9: Temperature control operation [MC-
VCOS(R)]
2: n/a
In the case of Cascade control, only
“0” or
“1” is selectable.
1
249
2. ORU
Input 2_Output change
rate limiter (up)
3)
0.0 to 1000.0%/seconds of manipulated
output
0.0: OFF
0.0
250
2. ORd
Input 2_Output change
rate limiter (down)
3)
0.0 to 1000.0%/seconds of manipulated
output
0.0: OFF
0.0
251
2.A O V E
Input 2_Action (high)
input error
2)
0: Control continues (with the latest output)
1: Manipulated output value at input error
(Manual mode)
The operation mode is switched to the
Manual mode and the Input 2_
Manipulated output value at input error is
output.
2: Manipulated output value at input error
(Auto mode)
The operation mode remains in the
Auto mode and the Input 2_Manipulated
output value at input error of is output.
When the error is recovered, the operation
mode is switched to the PID control.
2
252
2.A U N E
Input 2_Action (low) input
error
2)
0: Control continues (with the latest output)
1: Manipulated output value at input error
(Manual mode)
The operation mode is switched to the
Manual mode and the Input 2_
Manipulated output value at input error is
output.
2: Manipulated output value at input error
(Auto mode)
The operation mode remains in the
Auto mode and the Input 2_Manipulated
output value at input error of is output.
When the error is recovered, the operation
mode is switched to the PID control.
2
253
2. P S M
Input 2_Manipulated output
value at input error
2)
-5.0 to +105.0%
-5.0
254
2. R M V
Input 2_Manipulated
output value at STOP
2)
-5.0 to +105.0%
-5.0
255
2. P d A
Input 2_Start
determination point
1)
0 to Input 2_Input span
0: Operation starts from any start state
selected by Hot/Cold start
[Varies with the setting of the Decimal point
position.]
0
256
2.L P I D
Input 2_Level PID action
selection
3)
0: Switching by Memory area number
1: Switching by Set value (SV) (Level PID
action)
2: Switching by Measured value (PV)
(Level PID action)
0
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...