172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
313
Input 1_Proactive intensity [Parameter Setting Mode: Parameter group No. 51
(
Pn51
)]
Parameter symbol
Data range
Factory set value
1.P AC T
0 to 4
0: No function
2
To display “Input 1_Proactive intensity”, choose a setting other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input
2_Control action (Engineering mode). Additionally, a value other than 0 must
also be entered in the Input 1_Proportional band [heat-side] and the Input 1_
Integral time in the same memory area.
Input 2_Proactive intensity [Parameter Setting Mode: Parameter group No. 52
(
Pn52
)]
Parameter symbol
Data range
Factory set value
2.P AC T
0 to 4
0: No function
2
To display “Input 2_Proactive intensity”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2 (Engineering mode), AND choose a setting
other than “3 to 7
(Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input
2_Control action (Engineering mode). Additionally, a value other than 0 must
also be entered in the Input 2_Proportional band and the Input 2_Integral time in
the same memory area.
Input 1_FF amount [Parameter Setting Mode: Parameter group No. 51 (
Pn51
)]
Parameter symbol
Data range
Factory set value
1. F F
-100.0 to
100.0%
0.0
To display
“Input 1_FF amount”, choose “1 or 2” in Function block No. 57:
Bottom suppression function (Engineering mode), AND select other than MC-
(V)COS(R) pressure control for “Input 1_Control action” in Engineering mode:
Function block No. 51. Additionally, a value other than 0 must also be entered in
Input 1_Proportional band [heat-side] and Input 1_Integral time [heat-side] in the
same memory area.
Input 2_FF amount [Parameter Setting Mode: Parameter group No. 52 (
Pn52
)]
Parameter symbol
Data range
Factory set value
2. F F
-100.0 to +100.0%
0.0
To display “Input 2_FF amount”, choose “1 (FF amount is added by level)” or “2
(FF amount is forcibly added)
” in Function block No. 57: Bottom suppression
function (Engineering mode), AND choose “2-loop control/Differential temperature
control” or “Cascade control”, AND choose a setting other than “3 to 7 ( Pressure
control operation [MC-
VCOS(R)])” in Function block No. 52: Input 2_Control
action (Engineering mode). Additionally, a value other than 0 must also be
entered in the Input 2_Proportional band [heat-side] and the Input 2_Integral time
in the same memory area.
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...