172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
118
Memory area transfer timing
With SET signal ·········First, change the contact status to a desired No. referring to
the above table, and use a Close edge (Rising edge) of the
area SET signal. The area SET signal contact is: DI4 for 8
memory areas and DI5 for 16 memory areas.
After the c
ontact is transferred, it takes “up to 200 ms” until the action of
this instrument is actually selected.
Without SET signal ···· First select the memory area using contacts, then wait for
0.5 to 5.0 seconds (set in Function block No. 23: Area
switching time (without area set signal) (Engineering mode).
To change the Memory area without using the SET signal, “External mode” must
be set in Control area Local/External transfer (Operation transfer mode).
●
Area jump
The memory area will be switched to the area
set in the “Link area number” in the
Parameter setting mode after the Close edge or Open edge has been detected. If the
“Link area number” is not specified, the area number (which is the current number* +
1) will be selected.
*
In case the “Link area number” is not specified and the current control area No. is 16, the
area will not be changed.
Example:
If the current control area is “Memory area No. 1” and the “Link area
number” (set in area No. 1) is “No. 5,” the memory area will be changed to
No. 5 from No. 1 after the Area jump.
To perform an Area jump
“Digital input 1 (DI1) Close edge” or “Digital input 1 (DI1) Open edge,” or both of
these must be selected in Select Trigger type for Memory area transfer
(Parameter setting mode).
Contact closed
Contact open
Up to 200 ms
Close edge
Memory area No. B
Memory area No. A
Memory area
Memory area transfer
NOTE
Control area
Memory area No. 1
Control area
Memory area No. 5
Area jump
Link area number
No.5
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...