172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
68
235
TRK
SV tracking
0 to 3
0: No SV tracking function
+1: SV tracking at transferring
Remote/Local *
* Including Cascade mode transfer,
2-loop control/Differential temperature
control transfer
+2: SV tracking at transferring Auto/Manual
To select two or more functions, sum each
value.
1
236
Id d P
Integral/Derivative time
decimal point position
3) 4)
0: No decimal place
1: One decimal place
2: Two decimal places
0
237
STS
ST start condition
3) 4)
0: Activate the Startup tuning (ST) function
when the power is turned on; when
transferred from STOP to RUN; or when
the Set value (SV) is changed.
1: Activate the Startup tuning (ST) function
when the power is turned on; or when
transferred from STOP to RUN.
2: Activate the Startup tuning (ST) function
when the Set value (SV) is changed.
0
1)
Displayed when "Remote setting input", "Cascade control", "Control with PV select" or "2-loop control" are selected in "Select
function for Input 2" AND in the case of "2-loop control", both "Input 1_Control action" and "Input 2_Control action" are set to "PID
control" (0 or 1) or "Heat/cool PID control" (2).
2)
Displayed when "DI function selection" is set to "Area switching (without area set signal)".
3)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 1_Control action".
4)
Displayed when "2-loop control" is selected in "Select function for Input 2" AND "Pressure control operation [MC-(V)COS(R)]" is not
selected in "Input 2_Control action".
3.9.16 Function block No. 51: Input 1_Control (
1.ConT
)
No.
Symbol
Name
Data range
Factory
set value
User
set value
Fn51
Function block No. 51
This is the first parameter symbol of
Function block No. 51
238
1. OS
Input 1_Control action
0: PID control with Autotuning (direct action)
1: PID control with Autotuning (reverse
action)
2: Heating/Cooling PID control with
Autotuning [Cooling linear type]
3: Pressure control operation [MC-COS(R)-
3]
4: Pressure control operation [MC-COS(R)-
16, 15 to 50 mm]
5: Pressure control operation [MC-COS(R)-
16, 65 to 150 mm]
6: Pressure control operation [MC-COS(R)-
21]
7: Pressure control operation [MC-
VCOS(R)]
8: Temperature control operation [MC-
COS(R)-16]
9: Temperature control operation [MC-
VCOS(R)]
For cascade control, only 0 or 1 are
selectable.
In the case of Control with PV select, only
“0 to 2” are selectable.
Product
identificatio
n code
specified at
the time of
order.
239
1. ORU
Input 1_Output change
rate limiter (up) [heat-
side]
1)
0.0 to 1000.0%/seconds of manipulated
output
0.0: OFF
0.0
240
1. ORd
Input 1_ Output change
rate limiter (down) [heat-
side]
1)
0.0 to 1000.0%/seconds of manipulated
output
0.0: OFF
0.0
Summary of Contents for SC-F71
Page 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Page 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Page 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Page 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Page 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Page 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Page 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Page 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Page 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Page 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Page 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Page 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Page 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Page 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Page 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Page 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Page 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Page 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Page 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Page 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Page 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Page 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Page 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...